Type:

NYY

YVV

Standards:

IEC 60502-1

VDE 0271

Technical Specifications:

Rated Voltage (Uo/U): 0,6/1 [kv]

Max. Operating Temperature: 70 °C

Used Materials:

Copper (Cu), Stranded Wires – [Conductor]

Polyvinyl Chloride (PVC) – [Insulator]

Polyvinyl Chloride (PVC) – [Filling]

Polyvinyl Chloride (PVC) – [Sheath (Jacket)]

Size and Electrical Specifications:

Nominal Cross-Section
(mm²)
Outer Diameter
(mm)
Electrical Resistance at 20℃
(ohm/km)
Current Carrying Capacity / in ground
(A)
Current Carrying Capacity / in air
(A)
2×1,510,512,13222
2×2,511,57,414230
2×4134,615240
2×6143,086650
2×10161,839069
2×16181,1511592
2×25220,727150118
2×3524,50,524181145
2×5027,50,387215176
2×70310,268264224
2×9535,50,193317271
2×120390,153360314
3×1,51112,12719
3×2,5127,413625
3×4144,614734
3×6153,085943
3×1017,51,837959
3×16201,1510279
3×25240,727128106
3×35260,524157131
3×5029,50,387185159
3×7033,50,268228202
3×95380,193275244
3×120420,153313282
4×1,51212,12719
4×2,5137,413625
4×4154,614734
4×6163,085943
4×10191,837959
4×16211,1510279
4×25260,727128106
4×3528,50,554157131
4×50330,386185159
4×7037,50,272228202
4×9542,50,206275244
4×12046,50,161313282